Pressure from density
At equal reference pressure, air density follows the ideal-gas relation ρ = p / (R T). The model uses p = 101,325 Pa, R = 287.05 J/(kg·K) and g = 9.80665 m/s² (textbook constants).
The indoor-to-outdoor pressure difference at height z is Δp(z) = g(ρout − ρin)(z − zn). The neutral pressure plane zn is where the two pressures match.
Two-opening balance
For illustrative opening elevations zL = 2 m and zH = H − 2 m, equal mass flow gives zn = (AL² zL + AH² zH) / (AL² + AH²). The opening flow follows Q = Cd A √(2 |Δp| / ρ).
What is simplified
- One uniform indoor temperature and one outdoor temperature; no solar heating or room-by-room temperature variation.
- Two equivalent openings, a constant reference pressure and no wind, fans, duct losses or mechanical ventilation.
- A fixed illustrative floor area of 600 m² is used only to estimate building volume and air changes per hour.
- The seal limit is an illustrative warning threshold. The highlighted seam does not model fracture, leakage growth or a real product rating.