LIVE SECTION STACK FLOW · UPWARD
PRESSURE FIELD Δp(z) Warm interior · cooler exterior
ADJUST

Building conditions

ALL INPUTS · ILLUSTRATIVE
READ THE FIELD

Live measurements

MODEL OUTPUT
Stack pressure span— Paacross the full heightillustrative
Outdoor air flow— m³/hvolume at outdoor densityillustrative
Neutral plane height— mabove the lower openingillustrative
Air changes per hour— h⁻¹reference floor area · 100 m²illustrative

Cooler, denser outdoor air enters low down. Warmer indoor air rises and leaves near the roof.

MODEL AUDIT

Independent checks

CHECKS READY
∫Hydrostatic integral240-step integration vs exact pressure0.00%scaled
↕Neutral-plane rootBisection vs closed-form height0.00%scaled
⇄Mass continuityLower opening vs upper opening0.00%scaled
◉Orifice back-checkFlow-derived inlet pressure vs model0.00%scaled
FIELD EXPERIMENTTraverse the pressure columnRun a numerical pressure traverse and compare it with the textbook equation.
MODEL NOTESThe scienceEquations · assumptions · limitations +

Hydrostatic pressure difference

At height z, the indoor–outdoor pressure difference is Δp(z) = g(ρo − ρi)(z − zn). The density difference comes from the ideal-gas estimate ρ = p / (Rd T). The full-height pressure span is |ΔpH| = g |ρo − ρi| H.

textbook equations · illustrative conditions

Opening flow and the neutral plane

Each opening uses the orifice relation ṁ = Cd A √(2 ρup |Δp|). The neutral plane is where indoor and outdoor pressure match. It is found by balancing incoming and outgoing mass flow; the bisection result is checked against the closed-form result for the same two-opening model.

textbook relation · same Cd at both openings

What is simplified

The building is a single well-mixed air column at uniform indoor temperature, with still outdoor air, constant atmospheric pressure and two openings at the ends of the height. Wind, leakage distributed over the façade, internal partitions, thermal storage, humidity, mechanical fans and transient room-to-room flow are omitted. The reference floor area is 100 m² and is illustrative. Animated tracers show direction only; they are not a computational-fluid-dynamics solution.

illustrative model · not a building design tool

Constants and rendering

Textbook constants: gravitational acceleration g = 9.80665 m/s², dry-air gas constant Rd = 287.05 J/(kg·K), reference pressure p = 101325 Pa. The numerical pressure traverse uses a scaled 240-interval trapezoidal integration; the neutral-plane check uses bisection.

textbook constants · scaled numerical checks