Building conditions
Live measurements
Cooler, denser outdoor air enters low down. Warmer indoor air rises and leaves near the roof.
Independent checks
MODEL NOTESThe scienceEquations · assumptions · limitations +
Hydrostatic pressure difference
At height z, the indoor–outdoor pressure difference is Δp(z) = g(ρo − ρi)(z − zn). The density difference comes from the ideal-gas estimate ρ = p / (Rd T). The full-height pressure span is |ΔpH| = g |ρo − ρi| H.
Opening flow and the neutral plane
Each opening uses the orifice relation ṁ = Cd A √(2 ρup |Δp|). The neutral plane is where indoor and outdoor pressure match. It is found by balancing incoming and outgoing mass flow; the bisection result is checked against the closed-form result for the same two-opening model.
What is simplified
The building is a single well-mixed air column at uniform indoor temperature, with still outdoor air, constant atmospheric pressure and two openings at the ends of the height. Wind, leakage distributed over the façade, internal partitions, thermal storage, humidity, mechanical fans and transient room-to-room flow are omitted. The reference floor area is 100 m² and is illustrative. Animated tracers show direction only; they are not a computational-fluid-dynamics solution.
illustrative model · not a building design toolConstants and rendering
Textbook constants: gravitational acceleration g = 9.80665 m/s², dry-air gas constant Rd = 287.05 J/(kg·K), reference pressure p = 101325 Pa. The numerical pressure traverse uses a scaled 240-interval trapezoidal integration; the neutral-plane check uses bisection.