Inside the outdoor coil
The coil is below freezing, but the air is dry enough that little or no water vapour deposits as frost.
MODEL NOTESThe scienceEquations, assumptions and numerical checks
This is a deliberately compact model of moisture deposition and fin blockage on an air-source heat pump's outdoor evaporator. It isolates the frosting mechanism; it is not a complete refrigerant-cycle or product-performance model.
Moisture available to freeze
Water-vapour density at the coil surface is calculated from saturation pressure over ice. A positive difference between the incoming-air density and the surface saturation density drives deposition.
The mass-transfer coefficient uses a laminar flat-plate Sherwood correlation: Sh = 0.664 Re1/2 Sc1/3, with hm = Sh D/L.
From frost to blocked passages
The cubic relation is the laminar parallel-plate channel result: for a fixed pressure difference, flow is proportional to the cube of the open gap. The model applies it to a simplified repeating fin passage.
Defrost energy
The energy meter integrates the input needed to warm and melt the removed frost. A fixed useful-energy fraction represents heat that reaches the frost rather than the cabinet or outdoor air.
Constants and scale
- Vapour gas constant, 461.5 J kg⁻¹ K⁻¹TEXTBOOK
- Latent heat of fusion, 334 kJ kg⁻¹TEXTBOOK
- Ice heat capacity, 2.1 kJ kg⁻¹ K⁻¹TEXTBOOK APPROX.
- Vapour diffusivity, 2.5 × 10⁻⁵ m²/sTEXTBOOK APPROX.
- Effective fin area, 7 m²; frost density, 150 kg/m³ILLUSTRATIVE
- Clean-coil UA, 183 W/K; face area, 0.45 m²ILLUSTRATIVE
- Defrost heat fraction, 0.82; channel length, 0.35 mILLUSTRATIVE
- Integration step, 0.1 s; display time ×120SCALED
Independent numerical checks
What is simplified
The coil is represented by one uniform surface temperature and one effective fin area. The flat-plate transfer correlation is only an approximation for a real louvred coil. Frost density and the heat-transfer reduction exponent are illustrative. The fan is treated as fixed face velocity rather than a pressure-dependent fan curve. The model omits refrigerant flow, compressor control, condensate drainage, liquid-water refreezing, non-uniform frost crystals and detailed reverse-cycle thermodynamics. The low-airflow trip is an illustrative protection threshold, not a specification for any product.
All live outputs and preset conditions are illustrative, not a heat-pump rating or design tool. Physical constants marked textbook are reference values; the rest are explicitly identified as illustrative or scaled.