FIELD LAB / ENERGY SYSTEMS

Why Outdoor Heat Pump Coils Grow Frost and Lose Airflow

INTERACTIVE PHYSICS
AIR-SOURCE HEAT PUMP / EVAPORATOR

Inside the outdoor coil

FROST-FREE
WHAT YOU ARE SEEING

The coil is below freezing, but the air is dry enough that little or no water vapour deposits as frost.

Elapsed 0.0 min · illustrativeDefrost energy 0.000 kWh · illustrative
FROST MASS
0.0 g
ILLUSTRATIVE
FROST THICKNESS
0.000 mm
ILLUSTRATIVE
AIRFLOW
0.000 m³/s
ILLUSTRATIVE
HEAT PICKUP
0.00 kW
ILLUSTRATIVE
FIXED STEP 0.1 s · SCALED TIME ×120
MODEL NOTESThe scienceEquations, assumptions and numerical checks

This is a deliberately compact model of moisture deposition and fin blockage on an air-source heat pump's outdoor evaporator. It isolates the frosting mechanism; it is not a complete refrigerant-cycle or product-performance model.

Moisture available to freeze

pᵥ = RH · pₛ,water(Tₐ)
ρᵥ = pᵥ / [Rᵥ(Tₐ + 273.15)]

Water-vapour density at the coil surface is calculated from saturation pressure over ice. A positive difference between the incoming-air density and the surface saturation density drives deposition.

ṁf = hm A max(0, ρᵥ − ρᵥ,s,ice)

The mass-transfer coefficient uses a laminar flat-plate Sherwood correlation: Sh = 0.664 Re1/2 Sc1/3, with hm = Sh D/L.

From frost to blocked passages

δ = mf / (ρf Aeff)
gclear = max(0.05g, g − 2δ)
airflow ratio = (gclear/g)³

The cubic relation is the laminar parallel-plate channel result: for a fixed pressure difference, flow is proportional to the cube of the open gap. The model applies it to a simplified repeating fin passage.

Q̇ = UA (Tₐ − Tcoil) · airflow ratio0.7

Defrost energy

emelt = Lf + cice(0 − Tcoil)
ṁmelt = η Pheater / emelt

The energy meter integrates the input needed to warm and melt the removed frost. A fixed useful-energy fraction represents heat that reaches the frost rather than the cabinet or outdoor air.

Constants and scale

  • Vapour gas constant, 461.5 J kg⁻¹ K⁻¹TEXTBOOK
  • Latent heat of fusion, 334 kJ kg⁻¹TEXTBOOK
  • Ice heat capacity, 2.1 kJ kg⁻¹ K⁻¹TEXTBOOK APPROX.
  • Vapour diffusivity, 2.5 × 10⁻⁵ m²/sTEXTBOOK APPROX.
  • Effective fin area, 7 m²; frost density, 150 kg/m³ILLUSTRATIVE
  • Clean-coil UA, 183 W/K; face area, 0.45 m²ILLUSTRATIVE
  • Defrost heat fraction, 0.82; channel length, 0.35 mILLUSTRATIVE
  • Integration step, 0.1 s; display time ×120SCALED
LIVE VALIDATION

Independent numerical checks

DIFFERENCE FROM REFERENCE
Humidity ratio round-trip0.000%Recover RH from humidity ratio · illustrative
Frost pulse integration0.000%Fixed-step sum vs closed-form rate · illustrative
Fin-channel flow law0.000%Simpson integral vs cubic-gap solution · illustrative

What is simplified

The coil is represented by one uniform surface temperature and one effective fin area. The flat-plate transfer correlation is only an approximation for a real louvred coil. Frost density and the heat-transfer reduction exponent are illustrative. The fan is treated as fixed face velocity rather than a pressure-dependent fan curve. The model omits refrigerant flow, compressor control, condensate drainage, liquid-water refreezing, non-uniform frost crystals and detailed reverse-cycle thermodynamics. The low-airflow trip is an illustrative protection threshold, not a specification for any product.

All live outputs and preset conditions are illustrative, not a heat-pump rating or design tool. Physical constants marked textbook are reference values; the rest are explicitly identified as illustrative or scaled.