A counterflow exchanger transfers heat because the two streams keep a temperature difference along the coil.
LOCAL ENERGY BALANCE
dTh/dx = −(UA/Ch)(Th − Tc)
dTc/dx = −(UA/Cc)(Th − Tc)
TEXTBOOK ε–NTU SOLUTION
Q = ε Cmin(Th,in − Tc,in)
NTU = UA/Cmin, Cr = Cmin/Cmax
ε = [1 − e−NTU(1−Cᵣ)] / [1 − Cᵣe−NTU(1−Cᵣ)]
For Cr = 1, ε = NTU/(1 + NTU).
Textbook constantsWater cp = 4,180 J/(kg·K); ρ = 997 kg/m³ (approx.).
Illustrative inputsTemperatures, flow rates and UA are adjustable examples, not product specifications.
SimplificationsSteady state; single-phase water; constant properties; uniform UA; no heat loss to the room; no pressure drop or phase change.
Numerical methodRK4 integration with a shooting boundary condition is checked against the closed-form counterflow ε–NTU solution.
An educational physical model; not affiliated with any heat-pump manufacturer.