Pressure changes with height
The indoor and outdoor air columns have different densities. Their hydrostatic pressure difference varies with height:
Δp(z) = g (ρout − ρin) (z − zN)
Here z is height above ground, and zN is the neutral pressure plane where indoor and outdoor pressures match. A positive pressure difference means indoor pressure is higher.
Density and opening flow
ρ = p / (R T)
Dry-air density uses p = 101,325 Pa · textbook, R = 287.05 J kg⁻¹ K⁻¹ · textbook, and absolute temperature in kelvin. The gravitational acceleration is g = 9.80665 m s⁻² · textbook.
Q = Cd A √(2 |Δp| / ρ)
The orifice equation estimates volume flow through each opening. The upstream air density is used for each direction. The neutral plane is chosen so incoming and outgoing mass flow balance.
zN = (wL zL + wU zU) / (wL + wU)
The weights are the upstream density multiplied by the square of each effective opening area. The displayed result is also checked by numerically solving the mass-balance equation with bisection.
What is simplified
- Each opening is represented by one effective area and one shared discharge coefficient.
- Indoor and outdoor temperatures are uniform; density does not vary with height within either column.
- Wind, fans, doors opening, multiple leakage paths, heat transfer, moisture, and room-by-room pressure losses are omitted.
- The assumed floor plate is 8 m × 10 m · illustrative for the air-change estimate. The building drawing is a scaled schematic, not a surveyed structure.
All slider settings and building dimensions are illustrative. The ideal-gas relation, hydrostatic balance, and orifice-flow relation are standard textbook models; this is an educational calculation, not a building-design tool.