◈ FIELD LABBUILDING PHYSICS / INTERACTIVE EXHIBIT

VENTILATION · STACK EFFECT

Where a Building Breathes: The Neutral Pressure Plane

Warm air escapes above an invisible height while cool air enters below it. Move the openings to shift that boundary—and discover when natural ventilation stops working.

RUNNING
SECTION VIEW · ILLUSTRATIVE GEOMETRYWINTER / STACK FLOW
Outgoing air Incoming air Neutral plane
NEUTRAL PLANE HEIGHT—scaled · metres above floor
VOLUME FLOW RATE—textbook · m³/s
LOW OPENING PRESSURE—textbook · pascals, magnitude
AIR CHANGES PER HOUR—scaled · h⁻¹

Independent numerical checks

Three separate calculations test the live model. Percentage differences are shown against the analytical solution; near-zero differences are expected for this idealised system.

The science Equations, assumptions and limits

Hydrostatic pressure and buoyancy

Ideal-gas density: ρ = p/(R T), with p = 101325 Pa and R = 287.05 J/(kg·K). The indoor–outdoor pressure gradient is d(Δp)/dz = g(ρout − ρin), with g = 9.80665 m/s². The neutral plane is where Δp = 0.

Flow through openings

Each opening uses Q = Cd A √(2 |Δp| / ρ), with Cd = 0.62 (illustrative constant). Steady mass balance requires ρin Qout = ρout Qin. For two openings at heights z₁ and z₂, the neutral plane is solved algebraically using the two opening conductances. Flow direction changes with the temperature difference.

Three verification routes

The first check compares the analytical flow to a bisection solution of mass balance. The second integrates the pressure gradient numerically in 1,000 equal slices. The third compares a 60-second fixed-step volume accumulation with the exact integral of steady flow. All three use the same idealised assumptions but distinct numerical methods.

What is simplified?

The building is a single well-mixed zone with two small openings, constant temperatures, no wind, no fans, no leakage elsewhere, and no dynamic thermal feedback. Air is treated as incompressible across each opening, while ideal-gas densities determine buoyancy. Geometry and moving air streaks are illustrative; reported air-change rates use an illustrative 120 m² floor area. At equal temperatures, buoyancy-driven flow is zero and the neutral plane is physically undefined, shown at mid-height only as a display convention. This is an educational model, not a building-design calculation.

Made with 🤖 ChatGPT