Heat storage and buoyancy
The absorber and cavity air are two thermal nodes. The fixed-step RK4 solver integrates their coupled energy balances:
Cw dTw/dt = αIA − hiA(Tw−Ta) − heA(Tw−To) − εσA(Tw,K4−Tsky,K4)
Ca dTa/dt = hiA(Tw−Ta) − UgA(Ta−To) − ṁcp(Ta−To)
The long-wave term lets a clear sky cool the absorber below outdoor temperature. Stored heat delays the response after sunlight changes; that delay can briefly keep the updraft going, or produce a reverse draught after the panel cools.
Pressure and openings
Δp = p₀[e−gH/(RTa,K) − e−gH/(RTo,K)]
This is the difference between two isothermal hydrostatic pressure profiles. The two openings act in series:
Q = sgn(Δp) · CdAeff√(2|Δp|/ρ), Aeff = [Ain−2 + Aout−2]−1/2
Textbook constants: g = 9.81 m/s², R = 287.05 J/(kg·K), p₀ = 101325 Pa, cp = 1005 J/(kg·K), σ = 5.670374419 × 10⁻⁸ W/(m²·K⁴). Illustrative coefficients: α = 0.82, hi = 7.0 W/(m²·K), he = 5.5 W/(m²·K), Ug = 2.0 W/(m²·K), ε = 0.85 and Cd = 0.62. The clear-sky offset is 8 K (illustrative). The reference room volume is 75 m³ and chimney width is 1.2 m (both scaled).
What is simplified
The room is treated as a large, well-mixed reference zone held at outdoor temperature. Air in the chimney has one temperature; the absorber has one temperature; pressure is hydrostatic; openings are idealised orifices. Wind, leakage, humidity, solar-angle changes, stratification, detailed glazing optics and changing room temperature are omitted. The clear-sky temperature is set a fixed 8 K below outdoor air, an illustrative condition rather than a forecast.
Geometry, opening sizes, heat-transfer coefficients and preset starting temperatures are scaled or illustrative. The simulation demonstrates the direction and coupling of the effects; it is not a building-design calculator. The numerical checks compare the pressure head with a 200-layer (scaled) hydrostatic integration, the flow with a separately evaluated series-orifice relation, and the integrated energy change with the RK4 heat ledger.