ENERGY & INFRASTRUCTURE / 012
When a Building Breathes
Warm air rises. Wind pushes. Two openings decide whether a building can breathe.
—
—
Whole-building volume exchange
Well-mixed tracer experiment
01 / CHANGE THE CONDITIONS
Control the building
02 / MEASURE & VERIFY
Reality checks
Three independent calculations cross-check the airflow model. Percent differences are computed live, not hard-coded.
A hypothetical, well-mixed tracer is released indoors. Measure the time until 1/e remains, then compare with V/Q theory.
Press “Run tracer experiment” to start.
A taller separation between openings creates more buoyancy pressure for the same temperature difference.
03 / THE SCIENCEEquations, assumptions & limits⌄
Air density uses the ideal-gas approximation at fixed atmospheric pressure: ρ = p / (R T), with p = 101325 Pa and R = 287.05 J/(kg·K) (textbook constants). Temperatures are converted from °C to kelvin.
The pressure driving air from the lower to the upper opening is Δp = g H (ρout − ρin) + ½ ρout U² (Cp,low − Cp,high), with g = 9.80665 m/s² (textbook). Positive flow means lower-inlet to upper-outlet; negative means the reverse.
Two orifice resistances in series give Q = sgn(Δp) √(2|Δp|/ρref) / √[1/(Cd A1)² + 1/(Cd A2)²]. Here Cd = 0.62 (illustrative), ρref = (ρin + ρout)/2, and A1, A2 are effective opening areas. Air changes per hour are ACH = 3600|Q|/V.
The tracer model assumes a perfectly mixed, constant-volume room: dC/dt = −(|Q|/V)C. The simulation integrates this with a fixed 0.05 s step and an exact exponential update per step. Its theoretical e-folding time is τ = V/|Q|. A bisection solver independently finds the pressure split between openings; a separate series-resistance derivation and pressure/mass conservation provide the other checks.
Important simplifications: steady, incompressible orifice flow; constant pressure coefficients (Cp,low = 0.6, Cp,high = −0.3, illustrative); no turbulent building interior, heat transfer, humidity, leakage, or changing wind direction. Building geometry, airflow ribbons, tracer dots, and colours are illustrative, not CFD. A reverse flow is not necessarily hazardous; “no driving force” is the failed passive-ventilation regime in this model. Real buildings need more detailed ventilation design. This exhibit is not affiliated with any manufacturer or institution.