Can a building cool itself without a fan? Engineer an air path through glass, sunlight and gravity — then prove your design with the numbers.

01 / DIGITAL EXHIBIT

Inside the glasshouse

LIVE 3D MODEL
PERSPECTIVE / 3D● PAUSED
Drag a vent ↕ to change its height
Lower vent Upper vent
SIMULATED TIME00:00
INDOOR AIR32.0°CWell-mixed air model
STACK PRESSURE0.00PaUpward airflow
AIRFLOW RATE0.000m³/s0.0 changes / hour
HEAT BALANCE+0.00kWNet energy into the air
03 / MEASURE & COMPARE

Let the data speak

MODEL OUTPUT / SI UNITS

Temperature history

Indoor °C • simulated minutes

Vents apart, air in motion

Airflow m³/s versus separation (m)
Experiment ledgerCapture a snapshot, change the vents, then compare your design.
ReadingΔh (m)Aeff (m²)Q (m³/s)Indoor (°C)
No measurements yet. Press “Record reading” to start.
04 / ENGINEER'S TRIALS

Prove your thinking

0 / 8
INTERMEDIATE01 / 08

Calculating the air path

Answer the next question using the scientific model.

05 / THE SCIENCE BEHIND THE GLASS

Why does warm air rise?

IDEAL MODEL / REAL EQUATIONS
I

Pressure from buoyancy

Δp ≈ ρgh(Tᵢ − Tₒ)/Tᵢ,K

Warmer air is less dense. Over a height difference h, the density difference creates a small pressure difference that drives a flow.

II

Two vents work together

Q = CdAeff√(2|Δp|/ρ)

The lower and upper openings act as two restrictions in series. The effective area is 1 / √(1/A₁² + 1/A₂²).

III

Energy in, energy out

C dT/dt = Psun − Pwall − Pvent

Sunlight warms the glasshouse. Heat travels through its glazing and is carried away by air exchanging with the outdoors.

ⓘ
What this model assumes

One well-mixed indoor air temperature; constant air density 1.20 kg/m³ for mass flow; ideal two-opening stack flow, discharge coefficient 0.62, no wind, leaks, fans, humidity, shading or temperature stratification. Solar gain is a fixed fraction (0.42) of irradiance times floor area. Glazing has an effective U-value of 4.2 W/(m²·K); thermal capacity of soil, plants and furnishings is represented by 4.5 MJ/K. Vent drawings and the moving air dots are schematic, not computational fluid dynamics. Values are illustrative engineering estimates, not a building-control or horticultural design certification.

AFTER THIS EXHIBIT, YOU CAN…
  1. Calculate stack pressure.
  2. Predict how vent height and area affect airflow.
  3. Balance solar gain against ventilation cooling.

REAL-WORLD APPLICATIONS → Greenhouses, naturally ventilated classrooms, roof vents, solar chimneys and low-energy building design.