Governing model
The vertical temperature field follows a one-dimensional advection–diffusion balance with distributed wall heat loss:
∂T/∂t + u ∂T/∂z = Deff ∂²T/∂z² − λ(T − Tamb)
u = Q/A, λ = Gw/(ρcpV), where Gw is total wall-to-room conductance. The 180 L cylinder is divided into 96 finite volumes. A conservative finite-volume flux and fixed-step RK4 integration update each cell.
Physical constants
- Water density: 997 kg/m³ (textbook reference near 25 °C)
- Specific heat: 4,182 J/(kg·K) (textbook approximation)
- Storage volume: 0.180 m³ (fixed model geometry)
- Initial water temperature: 60 °C (illustrative)
Numerical checks
Energy ledger balance—
Periodic advection phase—
Diffusion eigenmode decay—
Checks compare independent numerical experiments with energy accounting or analytical solutions. Percent differences are recalculated from the current settings.
What is simplified?
The model is one-dimensional and assumes constant water properties, a uniform cross-section, equal inlet and outlet flow, and a well-defined effective axial diffusivity. It does not resolve the inlet jet, buoyancy-driven circulation, coils, thermostats, pipework, or detailed wall layers. The mixing coefficient is an illustrative control, not a universal measured property of domestic cylinders.
Temperatures, geometry and conductance are shown as illustrative operating conditions. Water properties are textbook reference values. The cylinder drawing is scaled for legibility rather than a manufacturing drawing.
Independent educational model. Not affiliated with any cylinder manufacturer or energy supplier.