Governing model
The vertical temperature field follows a one-dimensional advection–diffusion equation with a distributed side-wall heat loss:
∂T/∂t + u ∂T/∂z = αeff ∂²T/∂z² − λ(T − Tamb)
u = Q/A is the upward water velocity. αeff is the effective vertical diffusivity. λ = U S/(ρ cp V) represents heat transfer through the cylindrical side wall.
Numerics and reference values
The tank is divided into 96 equal-volume cells. Conservative face fluxes are advanced with fixed-step fourth-order Runge–Kutta integration (Δt = 1 s). The flow enters at the bottom at the selected inlet temperature and leaves at the top. The time step is below the advection and diffusion stability limits throughout the controls.
Textbook constants: water density ρ = 997 kg/m³ and specific heat cp = 4,180 J/(kg·K), treated as constant. The fixed tank radius is 0.22 m. Ambient and initial tank temperatures are 20 °C and 60 °C.
What is simplified
This is a one-dimensional vertical model, not a computational-fluid-dynamics model. It omits radial temperature gradients, inlet-jet geometry, buoyancy-driven circulation, coils, fittings, end-cap heat loss, temperature-dependent properties and phase change. The effective mixing coefficient stands in for unresolved vertical mixing. A real tank's value depends on its inlet diffuser, geometry, flow rate and operating history.
What is illustrative
Slider ranges, the 0.22 m radius, initial temperature, ambient temperature and side-wall coefficient are illustrative design conditions, not measurements from a particular installation. Readouts are calculated by this scaled model. The 10–90% thermocline width is a profile measure, not a certified tank-performance rating.