Why warm air escapes high above you—and where the pressure changes sign.
Air density follows the ideal-gas relation ρ = p₀/(R T), with illustrative constant pressure p₀ = 101325 Pa and textbook dry-air gas constant R = 287.05 J/(kg·K). Hydrostatic balance gives Δp(z) = g(ρₒ − ρᵢ)(z − zₙ), where textbook g = 9.80665 m/s².
For two openings at heights 0 and H, an idealised common-reference-density orifice model gives Q = Cᵈ √[2gH|ρₒ − ρᵢ|/ρᵣ] / √(1/Aₗ² + 1/Aᵤ²) and zₙ = H Aᵤ²/(Aₗ² + Aᵤ²). The sign of temperature difference determines flow direction. Vent speed is vₗ = Q/Aₗ. Vent pressure losses sum to the buoyancy head.
This is a steady, one-zone, Boussinesq-style educational approximation: density differences generate buoyancy, but one reference density is used for both volume flows. It excludes wind, mechanical fans, distributed leaks, turbulence, thermal stratification, and changing indoor temperature. Particle paths are illustrative tracers, not a computational-fluid-dynamics solution. All outputs are labelled scaled, not building-design predictions. The apparatus is generic and not affiliated with any manufacturer.