FIELD NOTES · BUILDING PHYSICS
MY SIMULATOR / ENERGY SYSTEMS
INTERACTIVE MODEL · WINDLESS CASE
THE STACK EFFECT

The Hidden Pressure Engine in Tall Buildings

A building can inhale below and exhale above — without a fan.

IDEALISED AIR COLUMN
WHAT YOU ARE SEEING

Warmer indoor air is lighter. It rises, drawing outdoor air in through low openings and pushing indoor air out through high openings.

THE SCIENCEEquations, assumptions and limits+

1. Density sets the pressure gradient

Air density is estimated from the ideal-gas relation, ρ = p / (R T), using p = 101,325 Pa and R = 287.05 J·kg⁻¹·K⁻¹. Temperatures are converted to kelvin. With uniform indoor and outdoor densities, the indoor-minus-outdoor pressure difference varies linearly with height:

Δp(z) = g (ρout − ρin) (z − zN)

g = 9.80665 m·s⁻² is textbook. The neutral pressure plane zN is the height where the two hydrostatic pressures are equal. For warmer indoor air, pressure difference increases with height; for warmer outdoor air, the direction reverses.

2. Each opening behaves like an orifice

At an opening, the magnitude of volume flow is approximated by the standard orifice relation:

Q = Cd A √(2 |Δp| / ρupstream)

The upstream density is outdoor density for inflow and indoor density for outflow. Signed mass flows are summed, and a bisection solver moves the neutral plane until total inflow equals total outflow. The discharge coefficient Cd = 0.62 is illustrative and fixed; real openings depend on geometry, screens, dampers and Reynolds number.

3. Two-opening analytical benchmark

With only a lower and an upper opening, mass continuity gives a closed-form neutral height. Let ρL and ρU be the upstream densities at the lower and upper openings for the current flow direction:

zN = (AU² ρU zU + AL² ρL zL) / (AL² ρL + AU² ρU)

The experiment compares this result with an independent bisection calculation while the upper opening area is swept. The main scene may include a third opening, so its neutral height can differ from the two-opening benchmark.

4. What is simplified and what is illustrative

  • Textbook constants: gravitational acceleration, ideal-gas constant for dry air and reference atmospheric pressure.
  • Calculated: densities, hydrostatic pressure differences, orifice flows, neutral-plane position, mass balance and air-change estimate.
  • Illustrative: the fixed discharge coefficient, the 300 m² floor plate used to estimate building volume, and the stylised locations and areas of the openings.
  • Not modelled: wind pressure, mechanical fans, leakage distributed continuously over the facade, temperature variation with height, humidity, buoyancy plumes, corridor partitions, door operation or transient thermal storage.
  • The building is represented by one well-mixed indoor air column and one outdoor air column with constant density. The model is a teaching approximation, not a ventilation design tool or a prediction for a real building.

5. Why the neutral plane moves

The neutral plane is not automatically halfway up a building. It shifts toward the larger effective opening because that opening can pass more air for a given pressure difference. A third opening can sit on either side of the neutral plane: it may become an inlet or an outlet. If indoor and outdoor temperatures are equal, the density difference and stack-driven pressure head vanish, so this idealised model predicts no stack flow and the neutral height is mathematically indeterminate; the display places it at mid-height for convenience.

Made with 🤖 ChatGPT