The Hidden Neutral Plane
in a Warm Building
Warm air rises. But halfway up a building, a hidden pressure boundary decides which openings breathe in—and which breathe out.
Measure against theory
Three independent cross-checks recompute the model without reusing its final answers. Percentage differences are displayed live.
Press Measure to compare integrated air volume against the steady-flow prediction.
The science Equations, assumptions and limitations +
Ideal-gas density: ρ = p / (R T), with p = 101325 Pa and R = 287.05 J kg⁻¹ K⁻¹ (textbook). Indoor–outdoor pressure difference is Δp(z) = g(ρout − ρin)(z − zn), with g = 9.80665 m s⁻² (textbook). Orifice volume flow is Q = Cd A √(2|Δp|/ρsource); the sign follows the pressure difference.
The neutral height zn is found by bisection on signed lower and upper opening mass flows, ensuring mass conservation. The flow display uses volumetric flow at the source density; air changes per hour are based on indoor volume. When both vents are closed, flow is zero and the neutral plane is undefined. When only one is open, this sealed, steady single-zone model also gives zero sustained through-flow.
Independent checks: a separate analytic pressure-gradient evaluation; a direct recomputation of the orifice law; and a trapezoidal numerical integral of the linear pressure profile. Each compares with a value produced through a distinct calculation path. These are numerical consistency checks, not independent experimental validation.
This is an illustrative stack-only model: no wind, fans, stratification, humidity, duct friction, transient room temperature, or distributed leaks. The animated particles depict direction and relative intensity, not individual tracked molecules. Air change rate assumes the stated floor area and room height. Not affiliated with any building equipment manufacturer.