MYSIMULATOR · ENGINEERING LAB

The Hidden Neutral Plane in a Ventilated Tower

Discover why warm buildings breathe in below a hidden height and breathe out above it.

LIVE PRESSURE FIELDRUNNING
The science Equations, assumptions and limits

Air density is ρ = p/(R T), with p = 101325 Pa and R = 287.05 J/(kg·K). The pressure gradient between inside and outside is g(ρout − ρin). For two openings at heights 0 and H, steady mass balance sets the neutral pressure height zn. At height z, Δp(z) = g(ρout − ρin)(z − zn).

Orifice flow is Q = CdA √(2|Δp|/ρ), with direction from high to low pressure. The solver balances mass flux through the two openings using bisection; each opening uses its source-side density. The displayed volume flow is a magnitude and air exchanges per hour are Q × 3600 / building volume.

Independent checks compare the numerical neutral height against an analytic two-opening mass-balance solution, compare calculated hydrostatic pressure with the density-gradient integral, and compare bisection flow against direct substitution of the analytic neutral height. Percentage differences use safe denominators; at zero draft, both values are exactly zero.

This is a steady, incompressible-orifice approximation with ideal-gas densities; temperature is uniform inside and outside, pressure variation with height is linear, and wind, duct losses, thermal stratification, turbulence and transient heat transfer are omitted. Tracer motion is illustrative rather than a computational fluid dynamics solution. The no-draft preset demonstrates the failure of buoyancy-only ventilation, not a structural failure. No company affiliation.