The Hidden Chimney: Stack Ventilation Lab

Watch a building breathe as warm and cold air compete with the wind.

ILLUSTRATIVE · AIRFLOW CUTAWAY
Calculated pressure · textbook— Pa
Volume flow · textbook— m³/s
Air changes · illustrative— h⁻¹
Independent numerical checks

Each comparison uses a separate numerical method. Differences are relative to a nonzero reference scale.

Hydrostatic integration vs closed form—
Bisection flow vs square-root solution—
Numerical mass balance vs continuity—
Ready to measure air exchange.
The science · equations, assumptions and limitations

Ideal gas: ρ = p/(R T), with textbook R = 287.05 J kg⁻¹ K⁻¹, p = 101325 Pa and g = 9.80665 m s⁻². Stack pressure: Δpₛ = g H (ρₒ − ρᵢ). Wind pressure: Δpᵥ = ½ ρₒ U² Cₚ, where signed Cₚ is an illustrative pressure coefficient. Net pressure: Δp = Δpₛ + Δpᵥ.

Two equal openings in series: effective area Aₑ = A / √2. Signed volumetric flow Q = sign(Δp) C𝒹 Aₑ √(2 |Δp| / ρᵢ). Air changes per hour = 3600 |Q| / V, with illustrative floor area 80 m² and V = 80H m³.

Numerical checks independently integrate the constant-density hydrostatic pressure gradient using midpoint quadrature; solve the nonlinear opening pressure loss by bisection; and integrate inlet/outlet mass flux across the 60-second experiment using a fixed timestep. Percent errors are measured against nonzero scales to avoid division by zero.

The air particles are illustrative tracers, not CFD. Density is uniform in each zone; flow is steady and incompressible through openings, with no vertical temperature gradient, turbulence, infiltration network, heat balance, duct resistance or occupant exposure prediction. A reversed or nearly stopped flow indicates failure of the intended passive ventilation direction, not structural failure. This is an educational model, not a building-design tool. Not affiliated with any manufacturer.

Made with 🤖 ChatGPT