The science · equations, assumptions and honest simplifications

Energy conservation

Q̇ room = Q̇ outdoor + Ẇ electric

For every second, the heat delivered indoors is the heat collected outdoors plus the electrical work supplied to the compressor. The displayed balance is calculated from the same model that drives the live values.

Heating coefficient of performance

COPheating = Q̇ room / Ẇ electric

A COP of 3.5 means that 1.0 kW of electrical input accompanies about 3.5 kW of heat delivered to the room. The additional energy is collected from outdoor air; it is not created from nothing.

Teaching approximation used by the sliders

COP ≈ clamp(0.42 × Troom,K / (Troom,K − Toutdoor,K + 8), 1.2, 5.0)

Temperatures are converted to kelvin for this ratio. The 8 K approach penalty and 0.42 factor are simple stand-ins for imperfect heat exchangers and real-world losses; the 5.0 cap keeps this miniature model within a plausible teaching range. They are not universal heat-pump constants.

What the miniature leaves out

The refrigerant loop is shown schematically: evaporator absorbs heat, compressor raises pressure and temperature, condenser releases heat, and expansion valve lowers pressure. The model does not solve refrigerant properties, phase equilibrium, humidity, defrost cycles, fan and pump electricity, pipe losses, cycling, or changing flow temperatures. Actual COP varies by equipment and operating conditions. The animated colour loop is explanatory, not a measured refrigerant state diagram.

Scale note: values are rounded to one decimal place for readability. The underlying calculations retain full floating-point precision.