THERMAL STORAGE · WATER SYSTEMS

Stratified Thermal Storage Tank Observatory

Watch a moving boundary separate hot water from cold, and discover why keeping that boundary sharp matters.

MODEL1D FINITE VOLUMEIllustrative 530 L vessel
OUTLET · SCALED20.0 °CBottom outlet
THERMOCLINE · SCALED— cm10–90% span · scaled
STORED HEAT · SCALED0.00 kWhAbove 20 °C · scaled
OUTLET RATE · SCALED0.00 kWRelative to 20 °C · scaled
LIVE VESSELTemperature structure
RUNNING
CoolerHotterColour is temperature, not material
i

Hot water is introduced at the top. It displaces cooler water downward while a narrow transition layer separates the two.

MODEL NOTESThe scienceEquations, assumptions and numerical checks +

Governing model

The tank is treated as a vertical, constant-area column. Temperature is represented by 72 well-mixed horizontal control volumes, indexed from bottom to top. The one-dimensional energy equation is

∂T/∂t + u ∂T/∂z = αeff ∂²T/∂z² − λ(T − Ta)

Here u = Q/A is signed superficial velocity, αeff is effective axial diffusivity, and Ta is ambient temperature. The wall-loss rate is λ = UP/(ρcpA), with cylindrical perimeter P = πD.

Advection uses first-order upwind face fluxes. Axial diffusion uses conservative face fluxes with zero diffusive flux at the ends. The wall term is integrated locally. All updates use a fixed 0.5 s step.

Constants and simplifications

  • Water density: 997 kg/m³ (textbook reference near 25 °C).
  • Specific heat: 4,182 J/(kg·K) (textbook reference).
  • Tank height 1.60 m and diameter 0.65 m (illustrative geometry; about 530 L).
  • Effective diffusivity and wall U-value are user-set (illustrative lumped parameters).

The model assumes a constant cross-section, incompressible water, fixed flow rate and a uniform wall-loss coefficient. It does not resolve inlet jets, radial circulation, buoyancy-driven plume shape, pipework, or temperature-dependent properties. The high-mixing preset represents diffuser failure by increasing axial mixing; it is not a CFD model of a broken diffuser.

Stored heat is the sensible energy above a 20 °C reference. Outlet heat rate uses the outlet temperature relative to the same reference.

Independent numerical checks

These checks run automatically using separate test profiles and analytical results.

Closed-volume diffusion energyChecking…
Fourier-mode decayChecking…
Uniform wall-cooling lawChecking…

Percentage difference is measured against the stated conservation law or analytical solution. The checks test numerical operators, not the completeness of the physical model.