Stack-Effect Ventilation
& Flow Reversal
Warm air can drive a building's ventilation without a fan. Change the temperature, openings and wind pressure to see when the flow reverses.
Independent numerical checks LIVE
The science +
Why air moves
In a two-opening building, indoor and outdoor air densities differ. For an ideal gas, ρ = p/(R T), where R = 287.05 J kg⁻¹ K⁻¹ and p = 101325 Pa. The ideal stack pressure over height H is Δp = g H (ρout − ρin), with g = 9.80665 m s⁻². The wind pressure contribution is Δpwind = ½ ρout Cw U². The combined driving pressure is Δpnet = Δp + Δpwind.
For two equal openings with area A and discharge coefficient Cd, the series resistance gives Q = Cd A √(|Δpnet|/ρmean) sign(Δpnet). Air changes per hour are 3600 |Q|/V. The ideal neutral pressure level for equal openings is H/2, and is shown only when a stack gradient exists. A distinct Bernoulli calculation with equivalent area A/√2 independently checks the opening model.
The animated tracers are illustrative, not fluid particles solved by computational fluid dynamics. The geometry is a cutaway diagram; building height, volume, wind coefficient, discharge coefficient, opening symmetry, temperature uniformity and steady pressure are model assumptions. The flow model is quasi-steady and ignores turbulence, duct losses, thermal stratification, leakage and transient temperature changes. Wind pressure coefficient is a user-adjustable signed parameter; a negative value represents an opposing wind-pressure arrangement. This exhibit is not affiliated with any building manufacturer.