Governing physics
The loop is driven by a density difference over a vertical separation:
Δpb = g H [ρ(T̄) − ρ(Tout)]
Flow settles where this buoyancy head balances Darcy–Weisbach pipe loss and local losses:
Δploss = (f L/D + ΣK) ρv²/2
The friction factor uses the laminar relation 64/Re and the smooth-pipe Blasius estimate in turbulent flow, blended through the transition region.
Collector and tank
Cp dTp/dt = AηG − Aa₁(Tp−Ta) − Q̇f
The collector-to-fluid heat exchange uses a plug-flow heat-exchanger effectiveness, ε = 1 − exp[−UA/(ṁcp)]. The two tank layers exchange water and heat while losing energy to ambient air. All three temperatures advance with fixed-step fourth-order Runge–Kutta integration (0.25 s per step).
Constants and assumptions
- Textbook: g = 9.81 m/s²; water heat capacity cp = 4180 J/(kg·K); water density follows a standard liquid-water correlation over 0–100 °C.
- Textbook: reference water density at 20 °C = 998.2 kg/m³.
- Illustrative: optical efficiency η = 0.74; collector loss coefficient a₁ = 4.2 W/(m²·K); collector UA = 200 W/K per m²; plate heat capacity = 12 kJ/(K·m²).
- Illustrative: 180 L two-layer tank, fixed pipe-loss coefficient ΣK = 5.5, and fixed tank insulation/mixing coefficients.
What is simplified
This is a lumped, single-phase water model. It does not resolve boiling, flashing, air locks, check valves, pump assistance, detailed collector optics, pipe heat loss, or three-dimensional stratification. The collector is represented by one thermal plate; the tank has two perfectly mixed layers. A high-temperature warning is an educational threshold, not a safety assessment. The schematic is not to scale.