loading...
Temperature along the matrix depth (cycle mean): exhaust gas, supply gas, matrix wall
Press the button: the finite-volume wheel is solved to its periodic steady state at 12 speeds and compared with the Kays and London correlation.
running...
The science
What a rotary regenerator does. A honeycomb of thin metal foil rotates slowly (a few to about 20 rpm) with half of its face in the warm exhaust stream and half in the cold fresh-air stream, flowing in opposite directions. The matrix stores heat while it is in the warm half and releases it in the cold half. Sensible-only wheels recover roughly 70 to 90 % of the temperature difference.
Effectiveness. With capacity rates Cex = ṁex cp and Csu = ṁsu cp, Cmin the smaller one:
ε = Q / (Cmin (Tex,in - Tout,in)), Q = Csu (Tsu,out - Tout,in) = Cex (Tex,in - Tex,out)
Two dimensionless numbers. The overall number of transfer units combines the two film resistances, and the matrix capacity ratio says how much heat the rotating metal can carry compared with the air:
NTU0 = 1 / [Cmin (1/(hA)ex + 1/(hA)su)], Cr* = Mw cw N / Cmin
For a very fast, heavy matrix (Cr* → ∞) the wheel behaves like a counterflow exchanger, εcf = (1 - e-NTU(1-Cr)) / (1 - Cr e-NTU(1-Cr)), which is NTU/(1+NTU) for balanced flows. For finite speed the Kays and London correlation applies:
ε ≈ εcf [1 - 1 / (9 (Cr*)1.93)]
The simulation. The page does not use the correlation to draw anything: it integrates the Schumann equations for gas and matrix on a grid of 24 cells along the flow times 48 angular cells. For every cell the air follows Tout = Tw + (Tin - Tw) e-NTU/Nx, the wall temperature is advanced exactly over the dwell time and the heat is taken from the air, so energy is conserved to round-off. The wheel is rotated one angular cell per time step until the cycle repeats. The correlation is only used as the independent comparison.
Heat transfer and pressure drop. Square channels of hydraulic diameter dh and foil thickness t: open fraction φ = (dh/(dh+t))2, wetted area per volume 4 dh/(dh+t)2. Laminar developing flow, Hausen: Nu = 3.66 + 0.0668 Gz / (1 + 0.04 Gz2/3), Gz = (dh/L) Re Pr, h = Nu k / dh. Pressure drop Δp = (56.9/Re)(L/dh) ρ u2/2 (fully developed square duct, f Re = 56.9); fan electric power = V̇ Δp / η.
Frost and condensation. The exhaust leaves at Tex,out. If it falls below the dew point of the room air (Magnus formula) water condenses on the matrix; below 0 C that becomes frost and the wheel must be slowed, bypassed or preheated. The page only flags it from the bulk outlet temperature, because the wall at the cold end of the exhaust side is colder than the outlet air.
Checks (run in the page). (1) heat lost by the exhaust equals heat gained by the supply with unbalanced flows (a convergence test); (2) a heavy fast matrix against the closed-form counterflow ε = NTU0/(1+NTU0); (3) the default wheel against the Kays and London correlation; (4) grid convergence between a coarse and a fine grid; (5) a barely turning light matrix recovers almost nothing; (6) for balanced flows the whole matrix temperature field is point-antisymmetric, T(a,x) + T(a+180°,L-x) = Tex + Tout (hot end and cold end, exhaust and supply swap roles); (7) for a heavy fast balanced wheel the cycle-mean matrix profile is the analytic straight line T(x) = Tex - ε ΔT x/L - ΔT (1-ε)/2 with ε = NTU0/(1+NTU0).
Simplifications. Sensible heat only (a real enthalpy wheel with a desiccant coating also moves moisture, which is not modelled; condensation heat is ignored); no leakage, carry-over or purge sector (these reduce real effectiveness by a few percent); uniform air distribution over the face; no axial conduction in the foil; constant air properties; the channel Nusselt number uses the circular-tube Hausen form for square channels (about 10 % off). The honeycomb in the 3D picture is magnified about eight times so it can be seen; the physics uses the slider dh. Stream colours are the gas temperature in each cell, interpolated.