Sweep the heat load and watch each pressure contribution build. Select a point on the curve to set the operating load.
Water properties are held at their 60 °C reference values; geometry and operating conditions are illustrative.
Mass flow is calculated from Q / hfg; the heat rate is then reconstructed independently from mass flow and latent heat.
The plotted total is the sum of liquid and vapour friction plus the signed hydrostatic head. The capillary ceiling is independent of heat load in this constant-property model, so the intersection defines the capillary transport limit.
Assumptions: steady one-dimensional transport; uniform saturated water properties at 60 °C; cylindrical laminar vapour core; Darcy flow through a homogeneous wick; constant effective length; no sonic, boiling, entrainment or viscous limit. Positive inclination places the condenser above the evaporator. Values are illustrative, not a design certification.
Independent numerical check: the displayed energy-closure readout reconstructs heat rate from ṁ × hfg and compares it with the entered heat load.