Capillary supply: ΔPcap = 2σ cos θ / rp. The wick meniscus creates pressure in proportion to surface tension and inversely to pore radius.
Wick loss: ΔPwick = μlLwṁ / (ρlKAw). The porous wick is represented with Darcy flow.
Tube loss: ΔPtube = 128 μLṁ / (πρd⁴). Liquid and vapour lines use laminar Hagen–Poiseuille flow; gravity contributes ρlgΔz.
Thermal balance: ṁ = Q / hfg. The capillary limit occurs when total pressure demand equals the available capillary pressure.
Simplifications: Steady one-dimensional flow, fixed water properties near 60 °C, constant properties, ideal circular passages, and no local fitting, sonic, entrainment, transient or boiling-superheat limits.