Buoyancy from heat
The source buoyancy flux is B = g P / (ρ cₚ T₀). The source-energy audit also uses an illustrative 6 L/s source-core flow to infer a temperature excess and independently reconstruct B from g′Q. Here g = 9.81 m s⁻², ρ = 1.204 kg m⁻³ and cₚ = 1005 J kg⁻¹ K⁻¹ are textbook reference values; T₀ is absolute room temperature.
Integral plume equations
For a steady, axisymmetric, top-hat plume, volume flux Q, momentum flux M and buoyancy flux B obey:
dQ/dz = 2 α √(π M)
dM/dz = B Q / M ; dB/dz = 0
The solver advances Q and M with fourth-order Runge–Kutta at a fixed vertical increment. The plume radius is b = Q / √(π M), centreline velocity is u = M/Q, and temperature excess follows ΔT = B T₀/(g Q).
Room and interface
The room is an illustrative 5 m × 4 m plan with balanced low-level supply and high-level extract. Ventilation flow is Qᵥ = ACH × V / 3600. If Qᵥ is below the plume flow at the ceiling, the interface is the height where Q(zᵢ) = Qᵥ. If extract exceeds the plume flow, the interface is pinned at the ceiling. With zero extract, no steady displacement interface exists.
What is simplified?
This is a steady integral plume model embedded in a conceptual room cutaway. The occupant is a heated source, not a detailed anatomical heat-transfer model. The room is treated as well mixed below a sharp interface; wall friction, cross-drafts, multiple occupants, moisture, radiation, transient layer filling and detailed diffuser jets are omitted. The plume is axisymmetric even though the room drawing is a two-dimensional section.
Illustrative: room dimensions, source heat, ventilation settings and entrainment coefficient are teaching inputs, not building measurements. Scaled: readouts and plume width are outputs of this reduced model. Textbook: constants and conservation relationships are identified as such.