FIELD STUDIESPHYSICS · BUILT ENVIRONMENT
INTERACTIVE EXHIBIT
NATURAL VENTILATION LAB / AIR PRESSURE

The building that breathes

Warm air rises, cool air sinks, and a quiet pressure boundary decides which way a building breathes.

Move the temperatures and vents.
Watch the airflow reorganise.
LIVE MODELA two-opening building section
UPWARD STACK
WHAT YOU ARE SEEING

The indoor air is warmer and less dense. Outside air enters low down, then the buoyant air column leaves through the upper opening.

FRESH AIR FLOW—m³/h · illustrative
Inlet volume rate
AIR CHANGES—h⁻¹ · illustrative
Based on model volume
NEUTRAL PLANE—m above floor · scaled
Inside = outside pressure
STACK PRESSURE—Pa across openings · illustrative
Top-to-bottom difference
MEASURE IT

Pressure survey

01

Take a set of virtual pressure readings at different heights. A straight-line fit estimates the pressure gradient, then compares it with the hydrostatic prediction.

⌁Run a survey to compare measured and theoretical pressure gradients.
31 samples · illustrative sensor · 0.01 Pa resolution
MODEL INTEGRITY

Numerical checks

02

Independent calculations test conservation, the neutral-plane solution and the hydrostatic pressure profile.

✓Mass continuity—illustrative check
✓Neutral plane: closed form vs bisection—illustrative check
✓Hydrostatic integration vs analytic pressure—illustrative check
These are numerical consistency checks, not field validation.
UNDER THE SURFACEThe science+

Governing equations

Ideal-gas density

ρ = p / (Rd T)

Hydrostatic pressure difference

Δp(z) = g (ρout − ρin) (z − zN)

Opening flow

ṁ = Cd A √(2 ρsource |Δp|)

Neutral pressure plane

zN = (ρLAL²zL + ρUAU²zU) / (ρLAL² + ρUAU²)

The source density at each opening depends on whether air is entering or leaving. The model solves the mass balance at steady state.

Constants and assumptions

  • Gravity: 9.80665 m/s² textbook.
  • Dry-air gas constant: 287.05 J/(kg·K) textbook.
  • Reference pressure: 101325 Pa textbook.
  • Discharge coefficient: user-controlled, illustrative.
  • Floor area: 48 m², scaled model assumption.

What is simplified

The building is one well-mixed air zone with two openings. Each zone has a uniform temperature and density. Wind, leakage, fans, internal heat sources, moisture, room-to-room paths and transient thermal storage are omitted. Flow is quasi-steady; only the visual tracers animate.

What is illustrative

Opening areas, temperatures, building dimensions, discharge coefficient and the sensor survey are teaching inputs, not measurements of a real building. The calculation is not a ventilation design tool.

An independent educational simulation. Not affiliated with any building, engineering or ventilation product manufacturer.