LIVE CUTAWAY scaled view
Follow the thermocline
A sharp thermocline keeps hot water at the outlet while the cold inlet layer waits below.
MODEL HEALTH
Three independent checks
Tank energy change vs inlet, outlet and wall heat flux.
Numerical gradient variance vs σ² = σ₀² + 2Dt.
Tracer-centre travel vs distance u × time.
textbook conservation and transport relations; illustrative numerical test columns and tank parameters.
TRY A MEASUREMENT
Run a diffusion pulse
Freeze the flow in a separate test column for a short pulse. Measure how much a Gaussian thermocline gradient broadens, then compare it with the diffusion law.
The scienceGoverning equations, assumptions and limits+
Temperature transport
The vertical water column is represented by a one-dimensional advection–diffusion equation with a side-wall heat-loss term:
u = Q/A is the upward bulk velocity. The model uses a conservative, fixed-step finite-volume update: upwind advection, centred diffusion, and a no-diffusive-flux boundary at each end. The inlet supplies water at Tin; the top is an advective outlet.
Jet mixing closure
α is the textbook thermal diffusivity of water near room temperature (1.43 × 10−7 m²/s). The coefficient and diffuser factor are illustrative: they make jet strength and diffuser action visible, but are not a universal empirical correlation. A real inlet needs geometry-specific validation.
Heat loss and useful energy
ρ and cp use textbook water properties (998.2 kg/m³ and 4182 J/kg K). Side-wall heat loss is applied uniformly to each cell. Useful stored heat is the water enthalpy above the current inlet-temperature reference.
What is simplified
- The vessel is a scaled vertical cylinder, represented as a one-dimensional column; radial circulation and local three-dimensional jets are not resolved.
- The diffuser is represented by one effectiveness parameter. The mixing closure is illustrative, not a substitute for CFD, experiments or a manufacturer's data.
- Water properties are held constant. Buoyancy, density variation, fittings, coil heat exchangers, top/bottom losses and changing tank volume are omitted.
- The drawing is a scaled explanatory cutaway. The temperature colours are computed from the cell temperatures, not a photograph or a measured tank.
Educational model only. It is not affiliated with a tank manufacturer and is not a certified engineering design tool.