MYSIMULATOR
ENERGY SYSTEMS / THERMAL STORAGE
INTERACTIVE FIELD NOTE

LIVE CUTAWAY scaled view

Follow the thermocline

STRATIFIED
Illustration of a stratified hot-water tank with a warm upper layer and cool lower layer
LIVE MODEL / TEMPERATURE FIELD illustrative
↔ Drag to inspect · 2D cutaway
SCHEMATIC OBJECT · SCALED GEOMETRY
SIMULATED TIME0.0 sillustrative
TOP OUTLET62.0 °Cillustrative
THERMOCLINE WIDTH0.18 millustrative
USEFUL STORED HEAT10.0 kWhillustrative
FRONT HEIGHT0.52 millustrative
EFFECTIVE DIFFUSIVITY0.29 µm²/sillustrative
↗

A sharp thermocline keeps hot water at the outlet while the cold inlet layer waits below.

MODEL HEALTH

Three independent checks

ERROR VS THEORY %
ΣEnergy balanceconservation law
0.000%

Tank energy change vs inlet, outlet and wall heat flux.

∂Diffusion pulseclosed form
0.000%

Numerical gradient variance vs σ² = σ₀² + 2Dt.

→Advection pulseclosed form
0.000%

Tracer-centre travel vs distance u × time.

textbook conservation and transport relations; illustrative numerical test columns and tank parameters.

TRY A MEASUREMENT

Run a diffusion pulse

Freeze the flow in a separate test column for a short pulse. Measure how much a Gaussian thermocline gradient broadens, then compare it with the diffusion law.

RESULT WILL APPEAR HERE
∑The scienceGoverning equations, assumptions and limits+

Temperature transport

The vertical water column is represented by a one-dimensional advection–diffusion equation with a side-wall heat-loss term:

∂T/∂t + u ∂T/∂z = Deff ∂²T/∂z² − λ(T − Tamb)

u = Q/A is the upward bulk velocity. The model uses a conservative, fixed-step finite-volume update: upwind advection, centred diffusion, and a no-diffusive-flux boundary at each end. The inlet supplies water at Tin; the top is an advective outlet.

Jet mixing closure

Deff = α + 0.12 u dport / (1 + 12 εdiff)

α is the textbook thermal diffusivity of water near room temperature (1.43 × 10−7 m²/s). The coefficient and diffuser factor are illustrative: they make jet strength and diffuser action visible, but are not a universal empirical correlation. A real inlet needs geometry-specific validation.

Heat loss and useful energy

λ = Uwall P / (ρ cp A)

ρ and cp use textbook water properties (998.2 kg/m³ and 4182 J/kg K). Side-wall heat loss is applied uniformly to each cell. Useful stored heat is the water enthalpy above the current inlet-temperature reference.

What is simplified

  • The vessel is a scaled vertical cylinder, represented as a one-dimensional column; radial circulation and local three-dimensional jets are not resolved.
  • The diffuser is represented by one effectiveness parameter. The mixing closure is illustrative, not a substitute for CFD, experiments or a manufacturer's data.
  • Water properties are held constant. Buoyancy, density variation, fittings, coil heat exchangers, top/bottom losses and changing tank volume are omitted.
  • The drawing is a scaled explanatory cutaway. The temperature colours are computed from the cell temperatures, not a photograph or a measured tank.

Educational model only. It is not affiliated with a tank manufacturer and is not a certified engineering design tool.