How Frost Chokes an Outdoor Heat-Pump Coil
A thin ice layer can quietly turn a useful heat exchanger into a bottleneck. Change the weather, watch the coil, and test when defrost earns its energy cost.
Weather & system controls
MODEL NOTESThe science+
Governing equations
Frost deposition: dm/dt = k (mcap − m). The rate coefficient k depends on humidity, airflow and how far the coil surface is below 0 °C. The solver uses fixed-step fourth-order Runge–Kutta integration.
Frost thickness: δ = m / (ρf A), using a representative coil face area and effective frost density.
Heat-pump limit: COPCarnot = Th / (Th − Tc); the illustrative operating COP is a fixed fraction of that reversible limit. Electrical input is W = Qout / COP, and source heat is Qin = Qout − W.
Defrost: a simplified reverse-cycle interval supplies a fixed share of electrical power to melt frost: dm/dt = −ηmelt P / Lf, bounded so frost mass cannot become negative.
What is simplified
This is a teaching model, not a manufacturer performance map or a refrigerant-cycle solver. It does not resolve refrigerant pressure, fan curves, local fin temperatures, droplet drainage, wind direction, controls hysteresis or building heat demand. The coil is represented by one average surface temperature and one average frost layer.
Frost density, coil area, deposition coefficient, compressor effectiveness, capacity curve and defrost power are illustrative. The latent heat of fusion of water ice, approximately 334 kJ/kg near 0 °C, is a textbook material property. Time is accelerated and displayed values are rounded; the model geometry is scaled.
Real equipment may use demand-based defrost logic and different refrigerants, coil geometries and control strategies. A real unit can behave differently from this deliberately compact model.