Governing model
The vertical temperature field follows a one-dimensional advection–diffusion equation with distributed heat loss:
∂T/∂t + u ∂T/∂z = αeff ∂²T/∂z² − (UA/ρcpV)(T − Troom)
Here, u is the signed plug-flow velocity, αeff is effective vertical thermal diffusivity, UA is the vessel heat-loss conductance, and ρcp is the water volumetric heat capacity.
Numerical method
The tank is divided into 56 equal-volume layers. Advection uses an upwind face flux; diffusion uses centred face gradients. The resulting semi-discrete equations and energy-budget integrals are advanced together with fixed-step fourth-order Runge–Kutta at 0.25 s per model step.
What is simplified
The vessel is represented as a one-dimensional column with constant cross-section. The model assumes incompressible water, constant density and heat capacity, a prescribed plug-flow velocity, and no radial temperature gradients. It does not solve buoyancy-driven circulation, inlet jets, turbulence, coil heat exchange, phase change or temperature-dependent water properties.
Textbook and illustrative values
Textbook water properties used for the energy scale are ρ = 997 kg/m³ and cp = 4180 J/(kg·K), representative of liquid water near room temperature. The corresponding molecular thermal diffusivity is about 1.4 × 10⁻⁷ m²/s. The vessel dimensions, operating conditions, heat-loss conductance and effective vertical mixing values are illustrative. The effective diffusivity is deliberately larger than molecular diffusivity to represent unresolved vertical mixing.
The 300 L-class vessel is a scaled teaching object, not a product design. The “mixing failure” preset raises effective diffusivity so that the layer boundary spreads; it is not a prediction of a particular tank's structural or safety limit.
Numerical checks
The energy check compares the change in stored sensible energy with integrated boundary heat flow minus integrated heat loss. The diffusion benchmark compares a separate finite-volume calculation with the analytic 10–90% width, 3.624√(αt), for a diffusing step. The plug-flow benchmark compares a separately advected pulse's numerical centroid shift with ut. Percentage differences are shown on the page.
All settings are illustrative unless explicitly marked textbook or scaled. This educational model is not affiliated with a tank manufacturer.