Governing equation
The vertical water column is represented by a one-dimensional advection–diffusion energy equation:
∂T/∂t + u ∂T/∂z = α ∂²T/∂z² − k(T − Tₐ)
u = Q/A is the upward water speed, α is effective axial thermal diffusivity, and k = UP/(ρcₚA) represents side-wall heat loss per unit water heat capacity. A diffusion-only reference spread over time t scales as √(2αt).
Numerical method
An illustrative 72-cell finite-volume column uses conservative upwind advection, centred diffusive face fluxes, exact half-step exponential wall cooling, and an illustrative fixed 0.25 s time step. The selected ranges keep the explicit transport update inside its stability limit. The canvas is a cutaway of the modelled cylinder, not a measured photograph.
What is simplified
The tank is treated as a vertical, constant-area column with incompressible water, constant density and heat capacity, one inlet at the base, one outlet at the top, and no internal coil or heater. The wall-loss model includes the cylindrical side only. It omits radial gradients, detailed inlet-jet circulation, buoyancy-driven turbulence, fittings, pipe heat loss, and temperature-dependent water properties.
Textbook and illustrative quantities
Water density (997 kg/m³) and specific heat capacity (4,182 J/kg·K) are representative textbook values near room temperature. Tank dimensions, flow settings, service threshold, wall coefficient and effective mixing coefficient are illustrative. The effective mixing coefficient is deliberately larger than molecular thermal diffusivity because it stands in for unresolved axial mixing as well as conduction.
Reading the experiment
The experiment advances a copy of the current temperature profile until the top outlet falls below the chosen 50 °C service threshold. Its ideal comparison is useful hot volume divided by flow rate: a plug-flow estimate that ignores thermocline spreading and wall losses. The difference shows how those effects change the time at which useful hot water runs out.
Educational model only. Results are illustrative, not a design tool for sizing or certifying a real hot-water system.