Where the heat boundary moves
A warm upper layer sits above cooler water. Hot inlet water enters at the top; the boundary between the layers moves down as the tank charges.
Measure the thermocline travel
Run a short, isolated charge test. The measured boundary movement is compared with the ideal displacement from flow rate and tank area.
The scienceMODEL · EQUATIONS · LIMITS
Governing model
The tank is represented by a vertical column of water. Temperature varies with height, while the cross-section is treated as uniform.
u = −Q/A during charging. The negative sign means the bulk displacement is downward. kw = UP/(ρcpA) represents heat loss through the cylindrical wall.
Water properties are held constant at density 997 kg/m³ (textbook) and specific heat capacity 4,180 J/(kg·K) (textbook).
Numerics and checks
The column uses 64 cells (scaled) and a fixed 0.5 s physics step (scaled). A conservative finite-volume flux form is advanced with fourth-order Runge–Kutta. The display runs at 60× playback (scaled); simulation time is not tied to the frame rate.
The page checks the energy ledger, a uniform-column exponential cooling solution, a diffusion step benchmark against its error-function solution, and the cylinder volume against the selected volume. The experiment separately compares measured front travel with Q·t/A.
What is simplified
The effective axial diffusivity is an illustrative lumped representation of inlet-jet mixing and other unresolved vertical mixing. The model does not resolve a three-dimensional inlet plume, radial temperature gradients, buoyancy-driven circulation, pipe heat capacity, fittings, or a real tank's internal diffuser. The wall-loss coefficient is uniform, and water density and heat capacity do not vary with temperature.
All control settings and tank dimensions are illustrative, not a product specification. The ideal front equation assumes plug displacement and is a reference, not a promise about a real installation.