Governing model. The vertical temperature field follows ∂T/∂t + v∂T/∂z = α∂²T/∂z² − k(T−Tₐ), with downward velocity v = −Q/A and wall-loss rate k = 4U/(ρcₚD). The inlet is held at the selected temperature; the bottom is an outflow.
Numerics. An 80-cell finite-volume column uses first-order upwind advection, conservative zero-flux axial diffusion and a fixed 0.1 s explicit step. The maximum slider settings remain inside the advection and diffusion stability limits. The animation advances at 60 simulated seconds per real second.
Independent checks. The energy ledger compares stored energy with inlet/outlet enthalpy flow and wall exchange. The plug-flow check compares a separate 768-cell scaled advection calculation with Δz = Qt/A. The 160-cell scaled diffusion experiment compares a finite-volume step profile with w₁₀₋₉₀ = 3.6248√(αt).
Simplifications. This is a one-dimensional, constant-property water model. It assumes a buoyancy-stable hot-over-cold arrangement and does not solve a three-dimensional inlet jet, natural convection, tank fittings, variable density or temperature-dependent properties. The diffuser is represented by effective axial diffusivity; a bypass preset illustrates increased entrainment rather than a CFD failure simulation.
Number labels. Water density and heat capacity are textbook reference values near room temperature. Operating settings and the 0.55 m tank diameter are illustrative. The 80-cell column, accelerated clock and drawn apparatus scale are scaled for the exhibit. All displayed outputs are calculated from the model. Positive wall exchange means heat leaves the water; a negative value means the room adds heat.