The hidden journey of heat
A cold day. A warm room.
Try it yourself
Change the same heat-pump model. Watch the energy balance and moving heat tracers respond. The room stays at 20°C in this simplified experiment.
The science · equations, assumptions and simplifications
QH = QC + W
Heat delivered to the room equals heat absorbed outdoors plus electrical work supplied to the compressor.
COPH = QH / W
At the starting settings, the model gives COP 2.39: about 2.39 kW of heat delivered for each 1 kW of electricity.
Closed-form teaching model. The ideal heating COP is approximated by Thot / (Thot − Tcold), with absolute temperatures in kelvin. The displayed COP is a fixed cycle-effectiveness fraction of that ideal value.
Assumptions. Indoor room target is 20°C; evaporator and condenser approach temperatures are each 5 K; steady-state energy flow; no defrost cycle, fan/pump electricity, pipe losses, cycling losses or changing refrigerant properties.
Honest simplification. This is an educational thermodynamic sketch, not a performance prediction for a real product. Real COP varies with refrigerant, compressor map, humidity, airflow, installation and operating conditions. Below-freezing operation can also trigger defrost and capacity limits.