How Frost Chokes a Heat Pump's Outdoor Coil
Watch water vapour turn to ice, airflow narrow, and a heating system decide when to defrost.
Water vapour is depositing as ice on the sub-zero evaporator. The growing layer reduces heat transfer.
What the system is doing
MODEL NOTESThe scienceEQUATIONS, ASSUMPTIONS & LIMITS +
Why frost changes the job
An air-source heat pump takes heat from outdoor air at an evaporator coil. When the coil surface is below the air's frost point, water vapour can deposit as ice. The layer adds thermal resistance and obstructs the narrow passages between fins. The compressor may then need a colder evaporating temperature to meet the same heating demand, reducing the heating coefficient of performance (COP).
Vapour available to freeze
w = 0.622 e / (p − e)
The humidity ratio w is calculated from vapour pressure e and atmospheric pressure p. Deposition is proportional to the positive difference between the air humidity ratio and saturation at the coil surface.
Mass and thickness
dm/dt = A ρair km max(wa − ws, 0)
dδ/dt = (dm/dt) / (ρf A)
Frost thickness δ follows from deposited mass, coil area A and an assumed bulk frost density ρf.
Temperature lift and COP
COPh = η Th / (Th − Tc)
Qh = UA (Ta − Tc) / (1 − 1/COPh)
The hot-side temperature Th follows the selected water supply plus a fixed approach. η is a second-law efficiency factor; Tc is solved from the requested heat output.
Energy to melt ice
dm/dt = −ηd Pd / Lf
During the simplified electric defrost, the compressor is paused and heater energy melts the frost using the latent heat of fusion Lf. The model stops a defrost when the coil is nearly clear or the cycle reaches its time limit.
What is simplified
The coil is represented by one average surface temperature and one effective UA value. Airflow loss and frost resistance are compact empirical factors, not a fin-by-fin pressure-drop calculation. The model uses a fixed atmospheric pressure, constant frost density, a single moisture-transfer coefficient and a fixed second-law efficiency. It omits refrigerant properties, fan and pump curves, condensate drainage, frost morphology, humidity stratification and building-side thermal storage.
What is illustrative
The clean-coil UA, transfer coefficient, surface area, frost density, efficiency, hot-side approach, defrost efficiency and controller timing are chosen to make the mechanisms visible. They are not a manufacturer's performance map and should not be used to size, diagnose or compare real equipment. The electric-heater defrost is a teaching simplification; many real heat pumps use a reverse-cycle defrost strategy.
Independent educational model. Not affiliated with or endorsed by any heat-pump manufacturer.