Governing equations
Vapour density: ρᵥ = RH · eₛ(Tₐ)/(RᵥTₐ). Saturation pressure uses the Buck water/ice fits; frost deposition uses saturation over ice.
Air-side transfer: hₐ = h₀√(u·φ), where u is fan command and φ = max(0.04, 1 − 2δ/g). The series resistance gives q″ = ΔT/[1/hₐ + δ/kf + 1/hᵣ].
Surface temperature: Tₛ = Tₐ − q″/hₐ. If Tₛ is below freezing, δ̇ = kₘ max(0, ρᵥ − ρᵥ,ice(Tₛ))/ρf.
Defrost: δ̇ = −ηP/(AρfLᶠ), bounded at zero. The live state uses fixed-step RK4 for frost growth; the melt check compares RK4 with the exact constant-rate result.
What is simplified
This is a single, well-mixed coil model. It treats frost thickness as uniform, uses a fixed frost density and conductivity, and represents the fan and refrigerant side with lumped coefficients. It does not resolve fin-by-fin temperature, droplets, frost porosity changes, refrigerant circuits, humidity gradients, or a real controller's sensor logic.
What is illustrative and textbook
Air-side and refrigerant-side coefficients, mass-transfer coefficient, coil area, clean airflow, frost density/conductivity, defrost power, efficiency, and controller timings are illustrative. Water-vapour gas constant Rᵥ = 461.5 J/(kg·K) and latent heat of fusion Lᶠ = 334 kJ/kg are textbook reference values. The displayed clock runs at a scaled rate of 60 simulated seconds per real second.
How to read the failure preset
The failed preset starts with a thick frost layer and automatic defrost disabled. The fin gap is never allowed to become negative: the model caps the layer before the two frost fronts mathematically cross. This represents a severely restricted coil, not a prediction of a particular product's failure point.