How frost forms
The coil surface is modelled at Ts = Ta − ΔT. When it is below freezing, vapour can deposit as ice if the ambient vapour density exceeds saturation over ice.
ρᵥ = pᵥ / (Rᵥ T)
ṁf = η hm A max(ρᵥ,a − ρᵥ,s, 0)
Saturation pressure uses a Magnus-type exponential fit. The vapour gas constant is 461.5 J kg⁻¹ K⁻¹ textbook. The transfer coefficient and capture factor are illustrative.
Why airflow falls
Mean frost thickness is δ = mf/(ρfA). Frost grows on both sides of a fin passage, so the blocked fraction is β = min(0.98, 2δ/g). Delivered flow follows a smooth resistance approximation, φ = max(0.08, (1 − β)1.55).
Heat pickup uses series thermal resistance and a flow correction: UA = A/(1/U₀ + δ/kf) × φ0.65; Q = UA ΔT. Frost density, conductivity, clean-coil conductance and fan law are illustrative model parameters, not product specifications.
Defrost and energy
At the selected blockage, the controller starts a four-minute melt cycle. Frost mass decays exponentially with a fixed time constant. The energy ledger includes fusion, warming ice to 0 °C and a constant heater-equivalent input. The ledger check compares the integrated total with the separately accumulated terms.
E = mmelt(Lf + cice ΔTice) + Pbase tdefrost
Latent heat of fusion is 333.7 kJ kg⁻¹ textbook. Defrost duration, melt time constant and base input are illustrative.
What is simplified
- The coil is a single, uniformly frosted surface; real frost is patchy and changes density.
- Airflow is represented by a fixed-speed resistance curve, not a measured fan map.
- Coil temperature is prescribed by one depression value rather than solved from a refrigerant circuit.
- Heat pickup is a coil-side estimate, not whole-system heating capacity or seasonal efficiency.
- Defrost is a lumped energy balance; drainage, refreezing, refrigerant transients and controls are omitted.
All live system values are illustrative; the accelerated clock is scaled. The 0 °C saturation-pressure comparison and listed material constants are marked textbook. This exhibit is an educational model, not a heat-pump performance prediction.