Vapour deposition
Ambient and surface vapour densities are estimated from saturation vapour pressures:
ρv = RH · pw(Ta) / (RvTa)
j = hm max(ρv − ρi, 0), dδ/dt = j/ρf
The frost layer is integrated with fixed-step fourth-order Runge–Kutta. The displayed thickness is a uniform-layer equivalent, not a reconstruction of individual ice crystals.
Fan and heat transfer
Δpfan = P0[1 − (Q/Q0)²]
Δpsys = 0.35P0(Q/Q0)² / φ²
Here φ = max(0.12, 1 − δ/(0.85g)) is the illustrative open-area factor. The operating flow is the intersection of the fan and system curves; the analytic result is checked against a bisection root.
UA = A / (1/hclean + δ/kf)
Q̇ = Ċ(Ta − Ts)[1 − exp(−UA/Ċ)]
The heat-transfer expression assumes a uniform coil surface and a single air stream with constant heat capacity. The independent energy check reconstructs the outlet-air temperature and calculates the air-side enthalpy drop.
Constants and assumptions
Textbook constants: water-vapour gas constant Rv = 461.5 J·kg⁻¹·K⁻¹; dry-air heat capacity cp = 1005 J·kg⁻¹·K⁻¹; ice fusion latent heat Lf = 333.5 kJ·kg⁻¹. These are standard approximate reference values.
Illustrative parameters: coil area 7.8 m², face area 0.52 m², clean-side heat-transfer coefficient 32 W·m⁻²·K⁻¹, frost conductivity 0.09 W·m⁻¹·K⁻¹, frost density 130 kg·m⁻³, and fan shut-off pressure 110 Pa. They are teaching assumptions, not specifications for a real product.
Simplifications: the model omits refrigerant circuitry, compressor power, coil-temperature feedback, liquid-water drainage, non-uniform frost bridging, fan blade details and the transient reversal of a real defrost cycle. Defrost is represented as an ideal heat input. A blocked-flow threshold is a visual warning, not a safety limit.
Every readout is an illustrative or scaled model result. The simulation is educational and is not a prediction of a particular heat pump's performance.