Glasshouse Heat Balance

2D section of the 3D glasshouse lab: watch every watt of sun, heater, wall loss, ventilation and soil exchange set the air temperature and humidity.

Switch to 3D

Presets

Playback

Apparatus

Model checks

The science

What is modelled

One well-mixed air node and one soil node exchange heat with the outside, the sun, a thermostatic heater and each other. Humidity follows a single water-vapour mass balance with condensation at saturation.

Equations

  • Air node Ca dT/dt = Qsun,air + Qheater - UA (T - Tout) - ρ cp (n V/3600)(T - Tout) - H (T - Tsoil) - Lv E.
  • Soil node with 77 % of the transmitted sun and a weak link to a 13 °C deep ground.
  • Vapour dm/dt = E - (nV/3600)(m/V - ρv,out); saturation by the Magnus formula.
  • Thermostat with ±0.35 K hysteresis.

Checks run in the page

  • Passive cooling against the closed-form exponential.
  • The air-node energy budget closes over 30 minutes.
  • Magnus saturation pressure against steam-table values.
  • The thermostat keeps air inside its band.

Honest simplifications

No CFD, no radiation exchange with the sky, no plant physiology and a uniform air node. Time runs at 120 simulated seconds per real second at 1x.

What to try
  • Choose Cold night and watch the heater cycle while the energy graph climbs.
  • Choose Sealed and humid: with almost no ventilation the humidity reaches saturation and condensation appears on the roof.
  • Raise ventilation on a sunny day and compare the heat lost through the vents with the wall loss.
Air, soil and outside temperature
Relative humidity against the comfort band
Power flows
Cumulative heater energy