Time scale speeds up the slow room thermal response.
Starting conditions
Changing this restarts the run.
Layers
Model checks
The science
Sensible cooling
The fan moves mass flow m = 0.17 (rpm/1600) kg/s over the coil. With an epsilon-NTU style effectiveness the supply temperature is Tout = Troom - 0.82 (1 - e-0.77 (0.17 / (m+0.025))) (Troom - Tcoil); heat removal is Q = m cp (Troom - Tout) with cp = 1006 J/(kg K).
Humidity
Water condenses on the coil when its surface is below the dew point of the room air. Humidity ratio w = 0.622 pv / (p - pv), with saturation pressure from the Magnus formula. The supply state is drawn on the straight coil-contact line from the room state toward the saturated coil state.
Room
One lumped thermal mass (75 kg of air-equivalent, 1006 J/kg/K) leaking toward 25.2 C with a 1200 s time constant.
Honest simplifications: illustrative model, not a refrigerant-circuit design tool; the compressor and outdoor unit are not modelled (electricity is a rough share); the parts are an original schematic assembly, not a specific commercial product. Time is accelerated by the slider.
What to try
- Pick Humid day: the supply point falls below the room point as water condenses and the drain pan fills.
- Dry air: the coil stays above the dew point and no condensate forms.
- Lower the fan: supply air gets colder but heat removal drops.