Power Usage Effectiveness is PUE = P_total / P_IT. Everything the IT load turns into heat must be removed by the cooling plant: free cooling through a cooling tower or dry coolers when the outdoor wet-bulb (or dry-bulb) temperature is low enough, and a vapour-compression chiller with COP about 0.5·T_evap/(T_cond - T_evap) when it is not. Warmer supply water (liquid cooling) widens the free-cooling window, which is why direct-to-chip and immersion reach lower PUE.
Rack power is limited by the air path: P_max = rho c_p V dT / f_air with at most 2 m³/s through a rack door, so air cooling stops near 20-40 kW per rack while liquid cooling can carry 100+ kW. The loop flow follows m = Q / (c_p dT). The top chart is the stacked power split, the lower-left chart is PUE against outdoor temperature at the chosen humidity, and the lower-right chart compares the per-rack limit of each cooling method with your rack power.
Checks: power closure (sum of parts equals total), heat closure (free cooling + chiller = heat load) and flow vs the textbook formula. Simplifications: steady state at one outdoor condition, constant humidity, no real chiller part-load curves. Same model module as the 3D page.