Smart Grid Frequency Balance

Swing equation, droop, battery and AGC on a single-area grid.

Presets

Controls

Live readouts

Independent checks

Experiment

Run the experiment to compare steady-state error and RoCoF with the formulas.
The science

An AC grid is balanced when total generation equals total demand. Any mismatch changes the kinetic energy stored in the spinning generators, so the frequency drifts. In per-unit form the aggregated swing equation is

2H d(df)/dt = Pm + Pbat + Pwind - dPload - D df

  • H is the inertia constant (seconds of rated power stored as rotation). Initial rate of change of frequency: RoCoF = -dP f0 / (2H).
  • Governor droop with turbine lag: Tg dPm/dt = Pagc - df/R - Pm. With droop alone the steady error is df = -dP / (D + 1/R); a battery responding proportionally adds a term Kb in the denominator.
  • Secondary control (AGC) integrates the error, dPagc/dt = -Ki df, and restores 50 Hz exactly once the balance is rebuilt.
  • Wind and solar are connected through inverters and add almost no inertia; the model reduces H by the wind share, H_eff = H (1 - wind), which makes the first seconds faster and deeper. Wind variability is an Ornstein-Uhlenbeck random signal.

Honest simplifications: one-area (copper-plate) model, no voltage or network limits, one lumped governor and turbine, no generator limits, battery without state-of-charge limits, 1000 MW base. A real smart grid also coordinates demand response, forecasting and voltage control, which are not modelled here. All parameter values are illustrative.

Checks shown in the page: steady frequency error against -dP/(D+1/R+Kb); AGC drives the error to zero; the initial df/dt against -dP/(2H); droop-only error against -dP R.