The science
Same model and the very same solver module as the 3D page. Single-phase, RMS, resistive loads, ideal transformers. The generator is an EMF Vs with internal resistance Rg = 0.4 ohm. An ideal step-up transformer of ratio k:1 multiplies voltage by k and divides current by k; the step-down transformer reverses it. Resistances seen through a k:1 transformer are multiplied by k2, so the whole network collapses to one series loop on the high-voltage side:
I2 = k Vs / (k2Rg + Rl + k2Rp), I1 = k I2, Vload = k Rp I2, 1/Rp = Σ 1/Ri (closed breakers)
Why transmit at high voltage. Ploss = I22 Rl = (Iload/k)2 Rl. Stepping the voltage up by k cuts the line current by k and the loss by k2 for the same load current. The middle graph compares the model with that 1/k2 law.
Maximum power transfer. From the load bus the source looks like Rg + Rl/k2 in series with an EMF Vs. Load power peaks when the load equals that resistance, but then half the generated power is wasted as heat, so real grids operate far from the matched point.
Independent checks. The live checks use a different route than the formulas above: a 2x2 nodal-voltage solve, Kirchhoff's current law at the load bus, an energy balance, the I2R loss recomputed from the load current, and a numerical search for the matched load. A sixth check evaluates the model at k and 2k with the load current held fixed and compares the loss ratio with 1/4.
Simplifications. Real grids are three-phase AC with reactive power, power factor, transformer losses and magnetising current, line inductance and capacitance, and skin effect. None are modelled; loads are fixed resistors and the out and return conductors are lumped in Rl. Dot speed, wire glow and window glow are qualitative. The sprites are Blender 5.2 renders of the 3D page's own models.