Depth-averaged heat conduction
∂T/∂t = α∇²T − q′(t) W(x,y) / (Cᵥ Δx²)
α = k/Cᵥ. The borehole source map W is a normalised Gaussian at each borehole. Positive q′ extracts heat; negative q′ injects it.
Seasonal load
q′(t) = (P/H) [cos(2πt/365 d) + b]
P is peak power per borehole, H is active depth, and b is the annual imbalance fraction in a 365-day illustrative cycle.
Line-source comparison
ΔT(r,t) = −q′ E₁(r²/4αt) / (4πk)
The pulse experiment compares the grid result with the infinite-medium line-source solution.
What is simplified
- Homogeneous, isotropic ground with constant conductivity and heat capacity.
- Vertical boreholes are represented by depth-averaged point sources in a horizontal plane.
- Fixed-temperature outer boundaries approximate distant ground recovery.
- No groundwater advection, grout resistance, pipe resistance, moisture migration, or vertical layering.
Numbers: material constants are marked textbook where sourced from standard heat-transfer ranges; operating settings and field results are illustrative. The field warning is a teaching indicator, not a certified design limit.