Hydrostatic pressure
Within a zone, pressure rises with depth:
p = ρ g h
ρ = 1,000 kg/m³ and g = 9.81 m/s² are textbook reference values for water near room temperature and standard terrestrial gravity. h is the vertical distance below that zone's tank water surface.
Zone sizing
nmin = ceil( H ρ g / plimit )
The model divides the total height into equal zones. Each break tank resets the pressure head, so the maximum static pressure in a zone occurs at its base.
Idealised pump power
Pin = ρ g Q H (n + 1) / (2 n η)
This is the sum for equal-height, cascaded zones with uniform demand per zone. It assumes each stage lifts the remaining demand by one zone height and uses the same overall efficiency.
What is simplified?
- Water is incompressible and has constant textbook density.
- Zones have equal height and their tank water surfaces sit at their upper boundaries.
- Each equal-height zone is assigned an equal share of total demand.
- Pipe friction, fittings, residual outlet pressure, tank drawdown, pump curves, control valves, and transient effects are omitted.
- The drawing is scaled for clarity; it is not a construction drawing or a building-services design tool.