Why the pressure reverses
At the same reference pressure, ideal-gas air density is ρ = p/(RairT), with Rair = 287.05 J/(kg·K) and g = 9.80665 m/s² textbook.
With uniform indoor and outdoor temperatures, the pressure difference varies with height: Δp(z) = p₀ + (ρout − ρin)gz. The neutral height solves Δp(zn) = 0.
Flow through each opening
Each vent has signed mass flow ṁ = sign(Δp) CdA√(2ρup|Δp|), where Cd = 0.62 is illustrative and upstream density depends on flow direction. A bisection solver finds p₀ such that the two vent mass flows sum to zero.
For two open vents, the textbook equivalent gives ṁ² = 2Cd²|ρout−ρin|gH · BC/(B+C), where B=Alower²ρup,lower and C=Aupper²ρup,upper.
Tracer and experiment
For a well-mixed room with no tracer source, dx/dt = −(ṁ/ρinV)x. Its exact solution is x(t) = x(0)e−kt; the theoretical half-life is ln(2)/k. Live tracer is integrated with fixed-step fourth-order Runge–Kutta; the experiment uses a separate RK4 calculation.
What has been left out
This is a textbook idealisation of a single, perfectly mixed zone with two sharp-edged openings, constant temperatures, dry ideal-gas air, zero wind and fixed ambient pressure. It excludes wind loading, duct losses, multi-floor compartmentalisation, infiltration, thermal transients and two-way exchange through a single vent. A blocked vent consequently gives zero circulation in this model. Architectural details, tracer particles and time acceleration are illustrative or scaled; their motion is not a CFD solution.
Independent educational model. No company affiliation.