Governing equations
The pipe is represented as a rigid liquid column with hydraulic inertance. The standpipe stores the difference between upstream pipe flow and downstream valve flow:
L / (gA) · dQ/dt = Hₛ − H − RQ|Q|
Aₜ · dH/dt = Q − Qᵥ − Qₛₚᵢₗₗ
Here, A = πD²/4, and R = [fL/D + K] / (2gA²). The valve discharge follows a smooth prescribed closure curve. The overflow uses a broad-crested-weir approximation.
What is simplified
- The main is a single lumped column. Distributed pressure-wave travel, pipe-wall elasticity, branches and reflections are not resolved.
- The Darcy friction factor is held constant. Minor-loss coefficient K, weir coefficient and crest width are illustrative.
- The source head is set so the chosen initial flow is steady with the standpipe at its initial level. The standpipe is open to atmosphere.
- If the tank drains to its base, air admission and column separation are outside this model. Overtopping is represented as a spillway flow.
Constants and labels
Gravitational acceleration g = 9.81 m/s² and water density ρ = 998 kg/m³ are textbook reference values. Geometry, operating conditions and fittings are illustrative. Live results and the drawing are scaled model outputs.
This is an educational lumped-parameter model, not a design or safety tool. Real surge protection requires a distributed transient analysis and site-specific engineering.