Pressure from buoyancy
For indoor and outdoor air at nearly uniform temperatures, the hydrostatic pressure difference varies with height:
Δp(z) = g (ρout − ρin) (z − zN)
The neutral pressure plane, zN, is where indoor and outdoor static pressure match. Airflow through each opening follows the orifice relation:
Q = Cd A · sgn(Δp) √(2|Δp| / ρref)
The neutral plane is found by requiring the signed flows to balance. For two openings with the same discharge coefficient and reference density, the closed-form height is:
zN = (AL² zL + AU² zU) / (AL² + AU²)
What is simplified
The model uses dry ideal-gas air at textbook atmospheric pressure (101,325 Pa), an illustrative discharge coefficient of 0.62, two openings at scaled heights, uniform indoor and outdoor temperatures, and no wind. It assumes steady flow and equal opening discharge coefficients. Real buildings have distributed leakage, doors, shafts, wind pressures, thermal stratification and changing weather.
What is illustrative
The building dimensions are scaled, opening areas are effective illustrative values, and moving tracers show flow direction rather than computational fluid dynamics. The virtual manometer rounds the modelled pressure difference; it is not a physical sensor. Constants and the 20°C dry-air density reference are textbook values.