The Invisible
Pressure Plane
A building can breathe without a fan. Temperature differences create a hidden pressure boundary that decides where air enters — and where it escapes.
Inside the pressure field
Warmer indoor air is lighter. Pressure is lower indoors near the base, so air enters low and escapes through the upper opening.
Numbers behind the flow
Independent numerical checks
Numerical bisection compared with the closed-form pressure-balance height.
Trapezoidal integration of the density gradient compared with the stack-pressure equation.
Incoming and outgoing mass flow rates must agree in steady state.
Computed flow compared with the combined two-opening orifice solution.
How quickly does the air turn over?
Imagine releasing a harmless tracer that mixes evenly through the building. Run a washout test and measure how long it takes for its concentration to fall by half.
06 / MODEL NOTESThe science+
Governing relations TEXTBOOK
Air density is estimated from the ideal-gas relation, ρ = p / (R T), using p = 101,325 Pa and R = 287.05 J kg⁻¹ K⁻¹.
Hydrostatic pressure varies with height as dp/dz = −ρg. The indoor–outdoor pressure difference is linear in height for constant densities. Its zero crossing is the neutral pressure plane.
At an opening, volume flow follows Q = CdA√(2|Δp|/ρ). The steady state balances mass flow, not necessarily volume flow, between the lower and upper openings.
The stack-pressure magnitude is Δp = gH|ρout − ρin|. The tracer follows the exact well-mixed solution C(t) = C₀e−Qt/V.
What is simplified MODEL SCOPE
The building is one well-mixed zone with uniform indoor and outdoor temperatures. Air is treated as incompressible within each zone, while density differences are retained in the hydrostatic and mass-flow calculations.
Only two openings are modelled. Wind pressure, mechanical fans, internal partitions, leakage distributed over the façade, temperature stratification, humidity, and transient pressure storage are omitted.
The 80 m² floor footprint used for air changes is illustrative. Opening areas, discharge coefficient, dimensions, and presets are illustrative inputs rather than measured properties of a real building.
The model describes idealised stack-driven exchange. Real buildings may have several neutral pressure levels and complex local flows. This educational simulation is not a design or compliance tool.