FN FIELD NOTESINFRASTRUCTURE / PHYSICS
INTERACTIVE STUDY · STACK EFFECT
BUILDING PHYSICS / NATURAL VENTILATION

The Invisible
Pressure Plane

A building can breathe without a fan. Temperature differences create a hidden pressure boundary that decides where air enters — and where it escapes.

ILLUSTRATIVE STUDY12/16VENTILATION
Textbook air-flow relations · illustrative single-zone building · no wind or mechanical fans
01 / LIVE CUTAWAY

Inside the pressure field

LIVE MODEL
pressure difference neutral pressure plane SCALED VIEW · NOT TO SCALE
WHAT YOU ARE SEEING

Warmer indoor air is lighter. Pressure is lower indoors near the base, so air enters low and escapes through the upper opening.

03 / LIVE MEASUREMENTS

Numbers behind the flow

ILLUSTRATIVE MODEL OUTPUTS
NEUTRAL PLANE↕
6.47 m
above the base · warm interior · illustrative
STACK PRESSUREΔp
16.29 Pa
bottom-to-top difference · illustrative
FRESH-AIR FLOW⇢
0.0840 m³/s
inlet volume flow · illustrative
AIR CHANGES↻
0.210 h⁻¹
based on an 80 m² footprint · illustrative
04 / MODEL INTEGRITY

Independent numerical checks

SELF-CHECKING
01Neutral-plane rootTEXTBOOK
0.000%difference

Numerical bisection compared with the closed-form pressure-balance height.

02Hydrostatic pressureTEXTBOOK
0.000%difference

Trapezoidal integration of the density gradient compared with the stack-pressure equation.

03Vent mass balanceTEXTBOOK
0.000%mismatch

Incoming and outgoing mass flow rates must agree in steady state.

04Orifice flow rateTEXTBOOK
0.000%difference

Computed flow compared with the combined two-opening orifice solution.

05 / TRY AN EXPERIMENT

How quickly does the air turn over?

Imagine releasing a harmless tracer that mixes evenly through the building. Run a washout test and measure how long it takes for its concentration to fall by half.

ILLUSTRATIVE EXPERIMENT · EXACT WELL-MIXED DECAY · MODEL TIME ACCELERATED
Theory: — Measured: run the test
06 / MODEL NOTESThe science+

Governing relations TEXTBOOK

Air density is estimated from the ideal-gas relation, ρ = p / (R T), using p = 101,325 Pa and R = 287.05 J kg⁻¹ K⁻¹.

Hydrostatic pressure varies with height as dp/dz = −ρg. The indoor–outdoor pressure difference is linear in height for constant densities. Its zero crossing is the neutral pressure plane.

At an opening, volume flow follows Q = CdA√(2|Δp|/ρ). The steady state balances mass flow, not necessarily volume flow, between the lower and upper openings.

The stack-pressure magnitude is Δp = gH|ρout − ρin|. The tracer follows the exact well-mixed solution C(t) = C₀e−Qt/V.

What is simplified MODEL SCOPE

The building is one well-mixed zone with uniform indoor and outdoor temperatures. Air is treated as incompressible within each zone, while density differences are retained in the hydrostatic and mass-flow calculations.

Only two openings are modelled. Wind pressure, mechanical fans, internal partitions, leakage distributed over the façade, temperature stratification, humidity, and transient pressure storage are omitted.

The 80 m² floor footprint used for air changes is illustrative. Opening areas, discharge coefficient, dimensions, and presets are illustrative inputs rather than measured properties of a real building.

The model describes idealised stack-driven exchange. Real buildings may have several neutral pressure levels and complex local flows. This educational simulation is not a design or compliance tool.

Made with 🤖 ChatGPT